Title :
Research of boundary protection unit based on phase information of the improved recursive wavelet transform for EHV transmission lines
Author :
Duan, J.D. ; Kuang, J. ; An, L.
Author_Institution :
Dept. of Electr. Eng., Xi´an Univ. of Technol., Xi´an, China
fDate :
March 29 2010-April 1 2010
Abstract :
On the basis of analyzing the frequency characteristics of EHV transmission line boundary, this paper presents a novel principle and algorithm of boundary protection unit for extra-high-voltage transmission lines. The protection algorithm utilizes the improved recursive wavelet transform (IRWT) to extract the desirable frequency components of fault-induced transient signals. And then the IRWT measures the phase information of the signal components and concludes the average frequency which is the highest frequency existing in transient signal. According the difference of the average frequency value of the extracted signals, an internal or external fault can be distinguished. The extensive PSCAD/EMTDC simulation results show that the new proposed protection algorithm is insensitive to fault type, fault resistance, fault location and fault initial angle. And the boundary protection unit based on IRWT phase information is feasible and effective.
Keywords :
fault location; power transmission lines; power transmission protection; recursive estimation; wavelet transforms; EHV transmission lines; PSCAD-EMTDC simulation; boundary protection unit; extra-high-voltage transmission lines; fault initial angle; fault location; fault resistance; fault-induced transient signals; improved recursive wavelet transform; phase information; Improved recursive wavelet transform; Line boundary; Phase information; Transient based protection;
Conference_Titel :
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location :
Manchester
DOI :
10.1049/cp.2010.0250