DocumentCode
3184300
Title
Experimental measuring of the earth faults currents in MV compensated networks
Author
Toman, P. ; Dvorak, J. ; Orsagova, J. ; Misak, S.
Author_Institution
Brno Univ. of Technol., Brno, Czech Republic
fYear
2010
fDate
March 29 2010-April 1 2010
Firstpage
1
Lastpage
5
Abstract
The MV compensated Networks in Czech Republic are operated as nonsymmetrical, that means as networks with non-transposed lines. In these networks the fault currents depend on the affected phase because the Petersen coil is tuned only for one value of earth current. The paper deals with influence of fault type on size of fault current and on the length of its transient phenomena. There are described experiments which were realized in distribution network held by E.ON Czech Republic. There were made a few different fault (low-impedance, spark gap arc, damaged MV cable, 1.6 k??, 4 k?? and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means forty eight experimental faults. During each experiment the shunting of affected phase was applied.
Keywords
earthing; fault currents; power distribution protection; transient analysis; E.ON Czech Republic; MV compensated networks; Petersen coil; distribution network; earth fault currents; nontransposed lines; transient phenomena; Compensated Networks Experimental Measurig; Earth Fault; Shunting Method;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location
Manchester
Type
conf
DOI
10.1049/cp.2010.0324
Filename
5522181
Link To Document