  • Abstract
    This paper proposed a method for modelling of power system fault diagnosis process. In this process, electrical power system fault diagnosis needs three kinds of information to identify fault components: protection-breaker associations, breaker-primary component (such as line, transformer, bus and so on) associations and protection-primary component associations. Firstly, the protection setting values were compared with short circuit calculation values to determine the protecting zone. I.e. determine protection-primary component associations. Then the component connecting topology trees were used for creating the Petri Nets model of possible fault components. Finally according to Petri Nets model the true fault primary devices were identified. At the same time, the false tripping or operating information were picked out.
  • Keywords
    Petri nets; fault diagnosis; power system faults; relay protection; Petri nets model; breaker-primary component; power system fault diagnosis; protection-breaker associations; protection-primary component associations; relay protection; topology trees; Petri net; Protection; fault diagnosis; setting values;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
  • Conference_Location
    Manchester
  • Type

    conf

  • DOI
    10.1049/cp.2010.0331
  • Filename
    5522188