DocumentCode
3184531
Title
Single phase fault detection technique based on transient current and its application in non-solid grounded network
Author
Bingyin, Xu ; Yongduan, Xue ; Jing, Li ; Yu, Chen
Author_Institution
Shandong Inst. of Eng., China
fYear
2001
fDate
2001
Firstpage
141
Lastpage
144
Abstract
Very low fault currents and unstable fault conditions make single phase to ground fault detection in non-solid grounded networks very difficult. Many fault detection techniques have been developed and proved unsatisfactory in practical application. A new single phase fault detection and faulty feeder selection method using transient zero sequence current is presented and evaluated in this paper. A fault detection and recording device is developed and installed in a substation. Recorded fault data proved the proposed technique. It should be pointed out that using the transient zero sequence component to detect single phase faults is not a brand new concept. But this technique was not practical until cost effective microelectronics based high speed transient signal acquisition circuits were available. Therefore success of the proposed fault detection method is due to the development of modern electronic techniques
Keywords
earthing; fault currents; fault location; power distribution faults; power distribution protection; power system transients; distribution networks; faulty feeder selection method; low fault currents; nonsolid grounded network; single phase fault detection technique; substation; transient current; transient zero sequence current; unstable fault conditions;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location
Amsterdam
ISSN
0537-9989
Print_ISBN
0-85296-732-2
Type
conf
DOI
10.1049/cp:20010120
Filename
929283