DocumentCode :
3184752
Title :
Impedance based fault location method for single phase to earth faults in transmission systems
Author :
Jamali, S. ; Shateri, H.
Author_Institution :
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran, Iran
fYear :
2010
fDate :
March 29 2010-April 1 2010
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents a new impedance based fault location method in the case of single phase to earth faults. This method utilized the measured impedance by distance relay and super imposed current factor, which is the ratio of postfault current to super imposed current, to discriminate the fault position on the line. This method is robust against the fault resistance. The presented method only uses the measured impedance by distance relay, the super imposed current factor and few data which could be achieved through the SCADA based databases.
Keywords :
earthing; fault location; power transmission faults; power transmission protection; relay protection; SCADA based databases; distance relay; earth faults; fault resistance; impedance based fault location method; postfault current; superimposed current factor; transmission systems; Fault location; Impedance based method; Measured impedance; Transmission line;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location :
Manchester
Type :
conf
DOI :
10.1049/cp.2010.0351
Filename :
5522208
Link To Document :
بازگشت