DocumentCode
3184771
Title
Adaptive distance protection in presence of UPFC on a transmission line
Author
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran, Iran
fYear
2010
fDate
March 29 2010-April 1 2010
Firstpage
1
Lastpage
6
Abstract
This paper presents an adaptive distance protection scheme in the presence of Unified Power Flow Controller (UPFC), one of the Flexible Alternating Current Transmission System (FACTS) devices. The presence of UPFC on a transmission line has a great influence on the measured impedance at the relaying point. The measured impedance itself depends on the power system structural conditions, pre-fault loading, and especially the fault resistance. In the presence of UPFC, its controlling and structural parameters as well as its installation point affects the measured impedance. Therefore, the conventional distance schemes might not fulfil the protective duties satisfactorily and new approaches are required.
Keywords
fault diagnosis; flexible AC transmission systems; load flow control; power transmission protection; FACTS devices; adaptive distance protection; fault resistance; flexible alternating current transmission system; power system structural conditions; pre-fault loading; unified power flow controller; Adaptive distance protection; FACTS devices; Measured impedance; UPFC;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location
Manchester
Type
conf
DOI
10.1049/cp.2010.0352
Filename
5522209