DocumentCode
3185593
Title
Adaptive reclosure using high frequency fault transients
Author
Li Youyi ; Xinzhou, Li Youyi Dong ; Bo, Z.Q. ; Chin, N.F. ; Ge Yaozhang
Author_Institution
Xi´´an Jiaotong Univ., China
fYear
2001
fDate
2001
Firstpage
375
Lastpage
378
Abstract
A new signal processing algorithm for arcing faults detection based on the high frequency current transient is presented in this paper. In transient faults, arc current extinguishes and then ignites, and this periodically disturbs fault current. After several cycles, when transient signals by the fault decay a lot, the arc disturbance can be identified by the wavelet transform. The feasibility of this algorithm has been tested by computer simulation
Keywords
arcs (electric); power system faults; power system transients; signal processing; wavelet transforms; adaptive reclosure; arc current; arc disturbance identification; arcing faults detection; computer simulation; fault current; high frequency current transient; high frequency fault transients; signal processing algorithm; transient faults; wavelet transform;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)