• DocumentCode
    3185676
  • Title

    New multi-ended fault location design for two- or three-terminal lines

  • Author

    Tziouvaras, D.A. ; Roberts, J.B. ; Benmouyal, G.

  • Author_Institution
    Schweitzer Eng. Labs. Inc., USA
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    395
  • Lastpage
    398
  • Abstract
    This paper presents a new fault location system for multiterminal power transmission lines. The algorithm used by this system is suitable for inclusion in a numerical protection relay, which communicates with remote relay(s) over a protective relaying channel. The data volume communicated between relays is sufficiently small to be easily transmitted using a digital protection channel. The new algorithm does not require data alignment, pre-fault load flow information, phase selection information, and does not perform iterations to calculate the distance to the fault. Pre-fault load flow, zero-sequence mutual coupling, fault resistance, power system nonhomogeneity, and current infeeds from other line terminals or tapped loads do not affect the fault location accuracy
  • Keywords
    fault location; power system relaying; power transmission faults; power transmission lines; power transmission protection; relay protection; transmission line theory; algorithm; digital protection channel; fault location accuracy; multi-ended fault location design; multiterminal power transmission lines; numerical protection relay; protective relaying channel;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
  • Conference_Location
    Amsterdam
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-732-2
  • Type

    conf

  • DOI
    10.1049/cp:20010183
  • Filename
    929346