DocumentCode :
3185791
Title :
Wavelet transform in the accurate detection of high impedance arcing faults in high voltage transmission lines
Author :
Kim, C.H. ; Kim, H. ; Aggarwal, R.K. ; Johns, A.T.
Author_Institution :
Sungkyhunkwan Univ., South Korea
fYear :
2001
fDate :
2001
Firstpage :
422
Lastpage :
425
Abstract :
This paper describes a new fault detection technique which involves capturing the current signals generated in a transmission line under high impedance faults (HIFs). Its main thrust lies in the utilisation of the absolute sum value of signal components based on the discrete wavelet transform (DWT). A sophisticated decision logic is also designed for the determination of a trip decision. The results presented relate to a typical 154 kV Korean transmission system, the faulted signals for which are attained using the well known Electromagnetic Transients Program (EMTP) software. The simulation also includes an embodiment of a realistic nonlinear HIF mode
Keywords :
EMTP; discrete wavelet transforms; electric impedance; fault location; power transmission faults; power transmission lines; power transmission protection; relay protection; 154 kV; EMTP software; Electromagnetic Transients Program; Korean transmission system; current signals capture; decision logic; discrete wavelet transform; high impedance arcing faults; high voltage transmission lines; signal components absolute sum value; wavelet transform;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location :
Amsterdam
ISSN :
0537-9989
Print_ISBN :
0-85296-732-2
Type :
conf
DOI :
10.1049/cp:20010189
Filename :
929353
Link To Document :
بازگشت