Zero-sequence voltages in unit-connected generator for different methods of grounding generator neutral
Author :
Fulczyk, M.
Author_Institution :
ABB Corp. Res., Krakow, Sweden
fYear :
2001
fDate :
2001
Firstpage :
499
Lastpage :
502
Abstract :
In this paper, the influence of parameters of the generator and transformer, the additional capacitance to ground of the generator breakers on the zero-sequence voltages in generators during faults in the stator winding and the power system was determined. The analysis of zero-sequence components was carried out for unit-connected generators of power up to 1200 MVA. The voltage zero-sequence components feeding the measuring element of the protections were determined at faults along the whole length of the generator stator winding
Keywords :
earthing; electric generators; electrical faults; machine protection; machine theory; power transformer protection; stators; generator breaker capacitance; generator neutral grounding methods; power system; stator winding faults; unit-connected generator protection; voltage zero-sequence components; zero-sequence voltages;