• DocumentCode
    3188724
  • Title

    Input filter pre-charge scheme for high power PWM-CSRs connected to a weak utility supply

  • Author

    Tomasini, Marco ; Feldman, Ralph ; Wheeler, Pat ; Clare, Jon C.

  • Author_Institution
    Department of Electrical and Electronic Engineering, The University of Nottingham, NG7 2RF, UK
  • fYear
    2010
  • fDate
    19-21 April 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    High power PWM Current Source Rectifiers are normally connected to the utility supply by means of a lightly damped LC input filter. Pre-charge schemes employing pre-insertion resistors are typically used to mitigate the overvoltage across the filter capacitors during the connection to the utility grid. However noticeable distortion of the utility grid voltage may still occur during the insertion of the input filter to the grid, particularly at low ratios of the supply fault level to the converter rated power. This paper proposes a pre-charge scheme which yields a smooth and controllable connection of the input filter to the utility grid along with total absence of overvoltage across the input filter capacitors.
  • Keywords
    PWM-CSR; input filter; pre-charge;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics, Machines and Drives (PEMD 2010), 5th IET International Conference on
  • Conference_Location
    Brighton, UK
  • Type

    conf

  • DOI
    10.1049/cp.2010.0126
  • Filename
    5522523