DocumentCode
3189250
Title
Application of Phasor Measurement Units (PMUs) for fault location in SEC-EOA interconnected network
Author
Al-Mohammed, A.H. ; Mansour, M.M. ; Abido, M.A.
Author_Institution
Saudi Electr. Co., Dammam, Saudi Arabia
fYear
2010
fDate
18-22 Dec. 2010
Firstpage
435
Lastpage
439
Abstract
This paper addresses the subject of fault location in interconnected networks using the Phasor Measurement Units (PMUs). As it is not economical to install PMUs in all the network buses, this paper also highlights a PMU placement technique based on the so-called Tree Search Method (TSM) to determine a near-optimal solution for the PMU placement problem. TSM application to a 115 kV system depicted from the Saudi Electricity Company-Eastern Operating Area (SEC-EOA) network is then presented. Mathematical formulation to calculate the fault distance is discussed. Simulation results obtained from both PSCAD and MATLAB to determine the locations of different types of faults are presented and discussed.
Keywords
fault location; mathematical analysis; power system measurement; search problems; trees (mathematics); MATLAB; PMU placement technique; PSCAD; SEC-EOA interconnected network; Saudi Electricity Company-Eastern Operating Area network; fault location; mathematical formulation; phasor measurement units; tree search method; voltage 115 kV; Circuit faults; Fault location; Phasor measurement units; Power transmission lines; Synchronization; Transmission line measurements; Fault Location; Phasor Measurement Unit (PMU); Synchronized Measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy Conference and Exhibition (EnergyCon), 2010 IEEE International
Conference_Location
Manama
Print_ISBN
978-1-4244-9378-4
Type
conf
DOI
10.1109/ENERGYCON.2010.5771720
Filename
5771720
Link To Document