DocumentCode
3195859
Title
Performance of HRC fuse and MCCB in low voltage distribution network
Author
Eduful, George ; Ekowcole, Joseph
Author_Institution
R&D, Electr. Co. of Ghana, Kumasi, Ghana
fYear
2011
fDate
20-23 March 2011
Firstpage
1
Lastpage
6
Abstract
In this paper, application of HRC fuses and MCCBs in low voltage distribution network is examined. Performance of HRC and MCCB are compared under a typical system performance condition. The law of equivalence of contact wear was used to determine life expectancy of MCCB. It is shown that MCCBs are not economically viable in areas where incidence of short-circuit faults are rampant. Where electro-dynamic stress associated with circuit interruptions is of a major concern, application of HRC fuses is proposed. The study goes further to recommend a suitable combination of MCCBs and HRC fuses as effective means of protecting distribution transformers.
Keywords
electric fuses; power distribution faults; power distribution protection; power transformer protection; short-circuit currents; HRC fuse; MCCB; contact wear equivalence law; distribution transformer protection; electro-dynamic stress; low voltage distribution network; short-circuit faults; Circuit breakers; Circuit faults; Earth; Fault currents; Fuses; Low voltage; Stress; Electro-dynamic stress; HRC fuse; Let-through Energy; MCCB; Short-circuits;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES
Conference_Location
Phoenix, AZ
Print_ISBN
978-1-61284-789-4
Electronic_ISBN
978-1-61284-787-0
Type
conf
DOI
10.1109/PSCE.2011.5772463
Filename
5772463
Link To Document