• DocumentCode
    3195859
  • Title

    Performance of HRC fuse and MCCB in low voltage distribution network

  • Author

    Eduful, George ; Ekowcole, Joseph

  • Author_Institution
    R&D, Electr. Co. of Ghana, Kumasi, Ghana
  • fYear
    2011
  • fDate
    20-23 March 2011
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    In this paper, application of HRC fuses and MCCBs in low voltage distribution network is examined. Performance of HRC and MCCB are compared under a typical system performance condition. The law of equivalence of contact wear was used to determine life expectancy of MCCB. It is shown that MCCBs are not economically viable in areas where incidence of short-circuit faults are rampant. Where electro-dynamic stress associated with circuit interruptions is of a major concern, application of HRC fuses is proposed. The study goes further to recommend a suitable combination of MCCBs and HRC fuses as effective means of protecting distribution transformers.
  • Keywords
    electric fuses; power distribution faults; power distribution protection; power transformer protection; short-circuit currents; HRC fuse; MCCB; contact wear equivalence law; distribution transformer protection; electro-dynamic stress; low voltage distribution network; short-circuit faults; Circuit breakers; Circuit faults; Earth; Fault currents; Fuses; Low voltage; Stress; Electro-dynamic stress; HRC fuse; Let-through Energy; MCCB; Short-circuits;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES
  • Conference_Location
    Phoenix, AZ
  • Print_ISBN
    978-1-61284-789-4
  • Electronic_ISBN
    978-1-61284-787-0
  • Type

    conf

  • DOI
    10.1109/PSCE.2011.5772463
  • Filename
    5772463