DocumentCode
3196821
Title
A directional current differential protection against CT saturation in two sides fed networks
Author
Rahmati, A.
Author_Institution
ECE Dept., Ilam Univ. Ilam, Ilam, Iran
fYear
2011
fDate
20-23 March 2011
Firstpage
1
Lastpage
5
Abstract
A phase angle comparison method for detection of current-transformer (CT) saturation and stability against mis-operation on heavy external faults in numerical current differential relay is presented in this paper. The proposed directional criterion is based on comparison of line currents phase angle of two sides of the power transformer. Defined criterion can differentiate saturation condition from normal condition and various internal faults. The merit of this method is demonstrated by simulation of different faults and saturation conditions on a power transformer using ATP/EMTP software.
Keywords
EMTP; current transformers; electrical faults; fault diagnosis; power system stability; power transformer protection; relay protection; ATP-EMTP software; current transformer fault; current transformer saturation detection; current transformer stability; directional current differential protection; external fault; internal fault; line current phase angle comparison method; numerical current differential relay; power transformer; Circuit faults; Current transformers; Fault currents; Harmonic analysis; Power system harmonics; Power transformers; Relays; CT saturation; differential relay; directional criterion; phase angle;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES
Conference_Location
Phoenix, AZ
Print_ISBN
978-1-61284-789-4
Electronic_ISBN
978-1-61284-787-0
Type
conf
DOI
10.1109/PSCE.2011.5772523
Filename
5772523
Link To Document