• DocumentCode
    3196821
  • Title

    A directional current differential protection against CT saturation in two sides fed networks

  • Author

    Rahmati, A.

  • Author_Institution
    ECE Dept., Ilam Univ. Ilam, Ilam, Iran
  • fYear
    2011
  • fDate
    20-23 March 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    A phase angle comparison method for detection of current-transformer (CT) saturation and stability against mis-operation on heavy external faults in numerical current differential relay is presented in this paper. The proposed directional criterion is based on comparison of line currents phase angle of two sides of the power transformer. Defined criterion can differentiate saturation condition from normal condition and various internal faults. The merit of this method is demonstrated by simulation of different faults and saturation conditions on a power transformer using ATP/EMTP software.
  • Keywords
    EMTP; current transformers; electrical faults; fault diagnosis; power system stability; power transformer protection; relay protection; ATP-EMTP software; current transformer fault; current transformer saturation detection; current transformer stability; directional current differential protection; external fault; internal fault; line current phase angle comparison method; numerical current differential relay; power transformer; Circuit faults; Current transformers; Fault currents; Harmonic analysis; Power system harmonics; Power transformers; Relays; CT saturation; differential relay; directional criterion; phase angle;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES
  • Conference_Location
    Phoenix, AZ
  • Print_ISBN
    978-1-61284-789-4
  • Electronic_ISBN
    978-1-61284-787-0
  • Type

    conf

  • DOI
    10.1109/PSCE.2011.5772523
  • Filename
    5772523