Title :
Loop selective direction measurement for distance protection
Author :
Holbach, Juergen ; Steynberg, Gustav
Abstract :
Distance relays achieve selective tripping by measuring all short circuit fault conditions within a settable reach. The direction of the fault (forward or reverse) is commonly determined with a dedicated measurement to ensure selectivity under all conditions. For the directional decision (measurement) a number of alternatives are available. This paper describes a loop selective direction measurement and illustrates by means of a typical fault why this is superior to a nonloop directional measurement such as those based on negative sequence quantities.
Keywords :
fault location; polarisation; power distribution faults; power distribution protection; power system relaying; relay protection; short-circuit currents; distance protection; distance relays; faulted loop voltage; loop selective direction measurement; memory voltage; negative sequence quantities; nonloop directional measurement; polarization; selective tripping; short circuit fault conditions; Circuit faults; Current measurement; Fault detection; Impedance measurement; Polarization; Protection; Protective relaying; Relays; Transformers; Voltage measurement;
Conference_Titel :
Protective Relay Engineers, 2005 58th Annual Conference for
Print_ISBN :
0-7803-8896-8
DOI :