• DocumentCode
    3199977
  • Title

    High Precision Temperature Control and Analysis of RF Deionized Cooling Water System

  • Author

    Tsai, Z.D. ; Chang, J.C. ; Liu, C.Y. ; Chen, J.R.

  • Author_Institution
    National Synchrotron Radiation Research Center, Hsinchu 30076, Taiwan, R. O. C. e-mail: ZDTsai@nsrrc.org.tw
  • fYear
    2005
  • fDate
    16-20 May 2005
  • Firstpage
    1057
  • Lastpage
    1059
  • Abstract
    Previously, the Taiwan Light Source (TLS) has proven the good beam quality mainly depends on the utility system stability. A series of efforts were devoted to these studies. Further, a high precision temperature control of the RF de-ionized cooling water system has been achieved to meet the more critical stability requirement. The paper investigates the mixing mechanism through thermal and flow analysis and verifies the practical influences. A flow mixing mechanism and control philosophy is studied and processed to minimize temperature variation which has been reduced from ± 0.1 °C to ± 0.01 °. Also, the improvement of correlation between RF performance and water cooling stability is presented.
  • Keywords
    Control system analysis; Cooling; Heat pumps; Light sources; Radio frequency; Stability; Temperature control; Temperature sensors; Valves; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Particle Accelerator Conference, 2005. PAC 2005. Proceedings of the
  • Print_ISBN
    0-7803-8859-3
  • Type

    conf

  • DOI
    10.1109/PAC.2005.1590657
  • Filename
    1590657