DocumentCode
3200164
Title
Analysis and Treatment of Electronic Voltage Transformers Exceeded Tolerance Problem
Author
Wang Jia-Ying ; Chen Hao-Lin ; Li Shen-Wang ; Zhang Guo-Qing ; Guo Zhi-Zhong
Author_Institution
Electr. Power Res. Inst. of Jilin Electr. Power Co. Ltd., Changchun, China
fYear
2012
fDate
8-10 Dec. 2012
Firstpage
359
Lastpage
362
Abstract
For speeding up of substation digitization processing, transformers do not need high efficiency signal output. In the high-voltage power system, the traditional voltage transformers have been gradually replaced by electronic voltage transformer. As electronic voltage transformer based on capacitive voltage divider´s excellent performance, it has become the best substitute of the traditional voltage transformer, widely used in power system. This paper presented the basic structure and analysis the experiment data. The main reasons of exceed tolerance problem is RC oscillating circuit and detention electric charge. By choosing a suitable value resistance, the problem has been solved. According to IEC60044-7, the ECVT reaches the requirement. It can completely meet the demands of the development of modern power.
Keywords
electric charge; potential transformers; substation automation; voltage dividers; IEC60044-7; RC oscillating circuit; capacitive voltage divider; electric charge; electronic voltage transformers; exceeded tolerance problem; high-voltage power system; substation digitization processing; Current transformers; Power system stability; Resistance; Transient analysis; Voltage measurement; Voltage transformers; detention electric charge; electronic voltage transformer; exceed tolerance;
fLanguage
English
Publisher
ieee
Conference_Titel
Instrumentation, Measurement, Computer, Communication and Control (IMCCC), 2012 Second International Conference on
Conference_Location
Harbin
Print_ISBN
978-1-4673-5034-1
Type
conf
DOI
10.1109/IMCCC.2012.88
Filename
6428921
Link To Document