Analysis and Treatment of Electronic Voltage Transformers Exceeded Tolerance Problem
Author :
Wang Jia-Ying ; Chen Hao-Lin ; Li Shen-Wang ; Zhang Guo-Qing ; Guo Zhi-Zhong
Author_Institution :
Electr. Power Res. Inst. of Jilin Electr. Power Co. Ltd., Changchun, China
fYear :
2012
fDate :
8-10 Dec. 2012
Firstpage :
359
Lastpage :
362
Abstract :
For speeding up of substation digitization processing, transformers do not need high efficiency signal output. In the high-voltage power system, the traditional voltage transformers have been gradually replaced by electronic voltage transformer. As electronic voltage transformer based on capacitive voltage divider´s excellent performance, it has become the best substitute of the traditional voltage transformer, widely used in power system. This paper presented the basic structure and analysis the experiment data. The main reasons of exceed tolerance problem is RC oscillating circuit and detention electric charge. By choosing a suitable value resistance, the problem has been solved. According to IEC60044-7, the ECVT reaches the requirement. It can completely meet the demands of the development of modern power.
Keywords :
electric charge; potential transformers; substation automation; voltage dividers; IEC60044-7; RC oscillating circuit; capacitive voltage divider; electric charge; electronic voltage transformers; exceeded tolerance problem; high-voltage power system; substation digitization processing; Current transformers; Power system stability; Resistance; Transient analysis; Voltage measurement; Voltage transformers; detention electric charge; electronic voltage transformer; exceed tolerance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Instrumentation, Measurement, Computer, Communication and Control (IMCCC), 2012 Second International Conference on
Conference_Location :
Harbin
Print_ISBN :
978-1-4673-5034-1
Type :
conf
DOI :
10.1109/IMCCC.2012.88
Filename :
6428921
Link To Document :
بازگشت