DocumentCode :
3209932
Title :
Compensation method for phase difference unbalance of output voltage in the three-phase triport UPS system
Author :
Harada, Koosuke ; Katsuki, Akihiko ; Mbouenda, Martin ; Tominaga, Fukutoshi
Author_Institution :
Dept. of Electron., Kyushu Univ., Fukuoka, Japan
fYear :
1988
fDate :
30 Oct-2 Nov 1988
Firstpage :
542
Lastpage :
544
Abstract :
A novel three-phase constant voltage transformer for the triport UPS (uninterruptible power supply) system is presented. In this circuit, the unbalance of the loads and the asymmetry of input source voltages are compensated by the ring connection of the secondary windings of respective linear inductors. It is concluded that this principle can be applied to the conventional triport transformer with magnetic shunts
Keywords :
compensation; potential transformers; uninterruptible power supplies; compensation method; constant voltage transformer; linear inductors; magnetic shunts; phase difference unbalance; ring connection; secondary windings; three-phase triport UPS system; uninterruptible power supply; Circuits; Electronics industry; Inductors; Industrial electronics; Phase distortion; Power system reliability; Thyristors; Uninterruptible power systems; Voltage control; Voltage transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 1988. INTELEC '88., 10th International
Conference_Location :
San Diego, CA
Type :
conf
DOI :
10.1109/INTLEC.1988.22405
Filename :
22405