• DocumentCode
    3210195
  • Title

    The steps to select a high horsepower variable frequency fan drive system

  • Author

    Beck, W.H. ; Ascherl, J.L.

  • Author_Institution
    Ross Hill Controls Corp., Houston, TX, USA
  • fYear
    1988
  • fDate
    12-14 Sep 1988
  • Firstpage
    81
  • Lastpage
    86
  • Abstract
    A method for evaluating an application for a high horsepower variable-frequency fan drive is discussed, whose steps include selection of the flow control method, simulation of the fan and system load line, definition of the fan shaft power, component selection, a harmonic and torsional analysis, and an economic evaluation. These steps are illustrated for a pair of 5000 hp blowers at the BASF plant in South Kerney, New Jersey
  • Keywords
    electric drives; 5000 hp; blowers; fan shaft power; flow control; variable frequency fan drive system; Analytical models; Blades; Control systems; Damping; Frequency; IEEE members; Power system harmonics; Shafts; Shock absorbers; Surges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 1988, Record of Conference Papers., Industrial Applications Society 35th Annual
  • Conference_Location
    Dallas, TX
  • Type

    conf

  • DOI
    10.1109/PCICON.1988.22419
  • Filename
    22419