DocumentCode :
3211770
Title :
Improving capacitive voltage transformer response and its impact on distance relay performance
Author :
Zare, Mohammad Hadi ; Mirzaei, Ahmad ; Abyaneh, Hossein Askarian
Author_Institution :
Yazd Univ., Yazd, Iran
fYear :
2012
fDate :
15-17 May 2012
Firstpage :
523
Lastpage :
528
Abstract :
Capacitive voltage transformer (CVT) has an ideal steady state response at the system power frequency, while its dynamic response is inferior. This may lead to the mis-operation of distance relays during a fault. This paper presents a new method in order to correct CVT transient response. The proposed method is able to eliminate transients emerging in the CVT output for various fault conditions and CVT parameters in the real-time. The simulation results reveal that the modified CVT exhibits a low percentage error. Moreover, the percentage overreach of distance relay connected to the modified CVT is considerably reduced.
Keywords :
fault diagnosis; potential transformers; relay protection; transient response; CVT transient response; capacitive voltage transformer response; distance relay protection performance; dynamic response; fault conditions; system power frequency; Inductance; Relays; Capacitive Voltage Transformer; Distance Relay; Overreach; Transient Response;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering (ICEE), 2012 20th Iranian Conference on
Conference_Location :
Tehran
Print_ISBN :
978-1-4673-1149-6
Type :
conf
DOI :
10.1109/IranianCEE.2012.6292413
Filename :
6292413