• DocumentCode
    3212338
  • Title

    Automated Monitoring of High-Resistance Connections in the Electrical Distribution System of Industrial Facilities

  • Author

    Yoon, Jangho ; Yun, Jangho ; Sang Bin Lee ; Wiedenbrug, Ernesto J.

  • Author_Institution
    Dept. of Electr. Eng., Korea Univ., Seoul
  • fYear
    2008
  • fDate
    5-9 Oct. 2008
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    High-resistance(R) connections due to poor contacts in the electrical distribution system can cause failures due to overheating, reduce efficiency, and pose safety risks in the industrial facility. The methods currently available for detection of high-R connections such as infrared thermography, resistance or voltage unbalance tests are inconvenient since they are off-line or walk-around type tests that do not provide continuous monitoring. In this paper, an automated technique for detecting high-R connections based on existing voltage and current measurements is proposed. The contact resistance, RHR, of the poor contact is estimated based on the voltage and current variation under startup and/or shutdown of the load for monitoring problems located upstream from the point of voltage measurement. For downstream problems, RHR is estimated based on the negative sequence current under steady state operation of the load. An experimental study on a 10hp induction motor load performed under simulated high-R circuit conditions verifies that poor contacts that exist upstream and downstream can be reliably detected without additional measurements. It is shown that the proposed technique can provide automated monitoring of the existence, location, and severity of high-R contacts for reliable, efficient, and safe operation of the industrial facility.
  • Keywords
    electric connectors; electric current measurement; electric resistance measurement; factory automation; induction motors; industrial power systems; power supplies to apparatus; power system measurement; voltage measurement; automated monitoring; contact resistance; current measurements; electrical distribution system; high-resistance connections; induction motor load; industrial facilities; negative sequence current; power 10 hp; steady state operation; voltage measurements; Computerized monitoring; Condition monitoring; Contacts; Electric resistance; Electrical safety; Industrial plants; Infrared detectors; Infrared surveillance; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2008. IAS '08. IEEE
  • Conference_Location
    Edmonton, Alta.
  • ISSN
    0197-2618
  • Print_ISBN
    978-1-4244-2278-4
  • Electronic_ISBN
    0197-2618
  • Type

    conf

  • DOI
    10.1109/08IAS.2008.172
  • Filename
    4658960