DocumentCode
3212338
Title
Automated Monitoring of High-Resistance Connections in the Electrical Distribution System of Industrial Facilities
Author
Yoon, Jangho ; Yun, Jangho ; Sang Bin Lee ; Wiedenbrug, Ernesto J.
Author_Institution
Dept. of Electr. Eng., Korea Univ., Seoul
fYear
2008
fDate
5-9 Oct. 2008
Firstpage
1
Lastpage
8
Abstract
High-resistance(R) connections due to poor contacts in the electrical distribution system can cause failures due to overheating, reduce efficiency, and pose safety risks in the industrial facility. The methods currently available for detection of high-R connections such as infrared thermography, resistance or voltage unbalance tests are inconvenient since they are off-line or walk-around type tests that do not provide continuous monitoring. In this paper, an automated technique for detecting high-R connections based on existing voltage and current measurements is proposed. The contact resistance, RHR, of the poor contact is estimated based on the voltage and current variation under startup and/or shutdown of the load for monitoring problems located upstream from the point of voltage measurement. For downstream problems, RHR is estimated based on the negative sequence current under steady state operation of the load. An experimental study on a 10hp induction motor load performed under simulated high-R circuit conditions verifies that poor contacts that exist upstream and downstream can be reliably detected without additional measurements. It is shown that the proposed technique can provide automated monitoring of the existence, location, and severity of high-R contacts for reliable, efficient, and safe operation of the industrial facility.
Keywords
electric connectors; electric current measurement; electric resistance measurement; factory automation; induction motors; industrial power systems; power supplies to apparatus; power system measurement; voltage measurement; automated monitoring; contact resistance; current measurements; electrical distribution system; high-resistance connections; induction motor load; industrial facilities; negative sequence current; power 10 hp; steady state operation; voltage measurements; Computerized monitoring; Condition monitoring; Contacts; Electric resistance; Electrical safety; Industrial plants; Infrared detectors; Infrared surveillance; Testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting, 2008. IAS '08. IEEE
Conference_Location
Edmonton, Alta.
ISSN
0197-2618
Print_ISBN
978-1-4244-2278-4
Electronic_ISBN
0197-2618
Type
conf
DOI
10.1109/08IAS.2008.172
Filename
4658960
Link To Document