• DocumentCode
    3212751
  • Title

    Analysis and comparison of islanding detection methods using a new load parameter space

  • Author

    Sun, Huili ; Lopes, Luiz A C ; Luo, Zhixiang

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
  • Volume
    2
  • fYear
    2004
  • fDate
    2-6 Nov. 2004
  • Firstpage
    1172
  • Abstract
    Anti-islanding protection is a mandatory feature for grid-connected inverters. The effectiveness of passive islanding detection methods (IDMs) is usually demonstrated by means of non-detection zones (NDZs) represented in a power mismatch space (ΔP × ΔQ). A number of active type IDMs with improved performance have been presented but their effectiveness cannot be compared using the ΔP × ΔQ space. This paper proposes a new load parameter space for comparing the effectiveness of IDMs where the influence of the load resistance can be easily assessed. Equations that represent NDZs for the ΔP × ΔQ and proposed load parameter space are derived and verified by simulation.
  • Keywords
    distributed power generation; invertors; load (electric); power distribution protection; reliability; antiislanding protection; grid-connected inverter; islanding detection method; load parameter space; load resistance; nondetection zone; power mismatch space; Circuit simulation; Circuit testing; Equations; Frequency; Inverters; Protection; RLC circuits; Reactive power; Sun; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, 2004. IECON 2004. 30th Annual Conference of IEEE
  • Print_ISBN
    0-7803-8730-9
  • Type

    conf

  • DOI
    10.1109/IECON.2004.1431741
  • Filename