DocumentCode :
3212751
Title :
Analysis and comparison of islanding detection methods using a new load parameter space
Author :
Sun, Huili ; Lopes, Luiz A C ; Luo, Zhixiang
Author_Institution :
Dept. of Electr. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
Volume :
2
fYear :
2004
fDate :
2-6 Nov. 2004
Firstpage :
1172
Abstract :
Anti-islanding protection is a mandatory feature for grid-connected inverters. The effectiveness of passive islanding detection methods (IDMs) is usually demonstrated by means of non-detection zones (NDZs) represented in a power mismatch space (ΔP × ΔQ). A number of active type IDMs with improved performance have been presented but their effectiveness cannot be compared using the ΔP × ΔQ space. This paper proposes a new load parameter space for comparing the effectiveness of IDMs where the influence of the load resistance can be easily assessed. Equations that represent NDZs for the ΔP × ΔQ and proposed load parameter space are derived and verified by simulation.
Keywords :
distributed power generation; invertors; load (electric); power distribution protection; reliability; antiislanding protection; grid-connected inverter; islanding detection method; load parameter space; load resistance; nondetection zone; power mismatch space; Circuit simulation; Circuit testing; Equations; Frequency; Inverters; Protection; RLC circuits; Reactive power; Sun; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Electronics Society, 2004. IECON 2004. 30th Annual Conference of IEEE
Print_ISBN :
0-7803-8730-9
Type :
conf
DOI :
10.1109/IECON.2004.1431741
Filename :
1431741
Link To Document :