• DocumentCode
    3213682
  • Title

    Improving voltage shift acceleration control methods for islanding detection considering reactive power

  • Author

    Pourbabak, Hajir ; Kazemi, A.

  • Author_Institution
    Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran, Iran
  • fYear
    2013
  • fDate
    17-18 Dec. 2013
  • Firstpage
    236
  • Lastpage
    240
  • Abstract
    Distributed generation plays an effective role in power systems. An important problem of DG operation is unwanted islanding phenomenon. Some methods have been introduced to detect islanding, such as passive and active methods. Voltage shift acceleration control is a kind of active methods that uses voltage positive feedback and it has low impact on network performance in normal condition. This paper proposes a modification in voltage shift acceleration control to decrease islanding detection time. Also it is shown that the impact of positive feedback gain during voltage variation is low.
  • Keywords
    acceleration control; distributed power generation; power distribution faults; voltage control; DG operation; distributed generation; islanding detection; positive feedback gain; power systems; reactive power; voltage positive feedback; voltage shift acceleration control; voltage shift acceleration control method; Acceleration; Distributed power generation; Frequency measurement; Inverters; Reactive power; Voltage control; Distributed generation; active methods; anti-islanding; communication-based methods; inverter; islanding detection; non-detection zone; passive methods; power mismatch;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Smart Grid Conference (SGC), 2013
  • Conference_Location
    Tehran
  • Print_ISBN
    978-1-4799-3039-5
  • Type

    conf

  • DOI
    10.1109/SGC.2013.6733815
  • Filename
    6733815