• DocumentCode
    3214180
  • Title

    Fault Detection and Protection of Three-Level Neutral-Point-Clamped PWM Voltage Source Converters

  • Author

    Wang, Fred ; Lai, Rixin ; Yuan, Xibo ; Luo, Fang ; Burgos, Rolando ; Boroyevich, Dushan

  • Author_Institution
    Center for Power Electron. Syst., Virginia Polytech. Inst. & State Univ., Blacksburg, VA
  • fYear
    2008
  • fDate
    5-9 Oct. 2008
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    This paper presents the detection and protection methods uniquely associated with three-level NPC voltage source converters. The line-to-ground fault can cause significant DC-link neutral voltage and therefore can be effectively detected and located through monitoring the voltage without extra hardware. The inner device short in the three-level phase-leg can lead to DC- link voltage unbalance and doubling the stress on capacitors and devices, which must be suppressed for the safe operation of the converter. Two overvoltage limiting methods are proposed to limit the overvoltage. The design of both the ground fault detection and overvoltage limiting has been covered in the paper. The schemes are verified through simulation and experiments.
  • Keywords
    PWM power convertors; fault location; overvoltage protection; fault detection; fault location; line-to-ground fault; overvoltage limiting methods; protection methods; three-level neutral-point-clamped PWM voltage source converters; Circuit faults; Electrical fault detection; Fault detection; Impedance; Phase modulation; Power conversion; Protection; Pulse width modulation; Pulse width modulation converters; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2008. IAS '08. IEEE
  • Conference_Location
    Edmonton, Alta.
  • ISSN
    0197-2618
  • Print_ISBN
    978-1-4244-2278-4
  • Electronic_ISBN
    0197-2618
  • Type

    conf

  • DOI
    10.1109/08IAS.2008.281
  • Filename
    4659069