DocumentCode :
3223295
Title :
Centralized normalization of voltage harmonics in the network with distributed nonlinear load by the third-order filters
Author :
Kovernikova, L.I.
Author_Institution :
Melentiev Energy Syst. Inst., SB RAS, Irkutsk, Russia
fYear :
2010
fDate :
15-18 June 2010
Firstpage :
148
Lastpage :
151
Abstract :
The paper studies the problems on centralized normalization of harmonic voltages in the network with distributed nonlinear loads by the passive third-order filters. The nonlinear loads are connected to the extended HV network at practically equal distances. Each nonlinear load is of sufficiently high power and causes sizable distortions in the supply network. The harmonic voltage values at the nodes of nonlinear loads connection to the supply network exceed the limits established by the standard. The paper addresses the problems of choosing the passive third-order filters: choice of the node for filter installation, calculation of filter parameters, evaluation of the efficiency of chosen filters for centralized normalization of harmonic voltages at the network nodes. An example of choosing filters for the real 220 kV network supplying power to traction loads is given.
Keywords :
harmonic distortion; power conversion harmonics; power harmonic filters; centralized normalization; distributed nonlinear load; third-order filters; voltage harmonics; Capacitors; Distortion measurement; Frequency; Joining processes; Passive filters; Power harmonic filters; Rail transportation; Substations; Transmission line measurements; Voltage; centralized normalization; harmonic distortion; harmonic limits; harmonic measurement; passive filter;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Nonsinusoidal Currents and Compensation (ISNCC), 2010 International School on
Conference_Location :
Lagow
Print_ISBN :
978-1-4244-5436-5
Type :
conf
DOI :
10.1109/ISNCC.2010.5524500
Filename :
5524500