DocumentCode
3232046
Title
Condition assessment of the health index for power transformer
Author
Haema, J. ; Phadungthin, R.
Author_Institution
Dept. Electr. Eng. Technol., King Mongkut´s Univ. of Technol. North Bangkok, Bangkok, Thailand
fYear
2012
fDate
18-20 Sept. 2012
Firstpage
1
Lastpage
4
Abstract
This paper is performed in order to estimate the overall condition of transformer, which is considered by 21 test methods : Dissolved Gas Analysis, Load History, Power Factor, Thermo Scan, Oil Quality, Furan, General Condition, Bushing, Surge Arrester, Conservator Tank, Main Tank, Hot Line Oil Filter, Radiator and Cooling System, Transformer Control Cabinet, Neutral Ground Reactor (NGR), Protection Equipment, Regulating PT, OLTC Compartment, OLTC Control Cabinet, DGA of OLTC, and OLTC Oil Quality. The condition assessment for transformer is performed by the analysis of each method, indicated by scoring and weighting factor of each tests. Furthermore, the overall condition and the result from 21 test methods indicated by this analysis result in the ability to effectively plan the maintenance of power transformer.
Keywords
maintenance engineering; power transformer testing; Furan; NGR; OLTC compartment; OLTC control cabinet; OLTC oil quality; bushing; conservator tank; cooling system; dissolved gas analysis; general condition; health index condition assessment; hot line oil filter; load history; main tank; neutral ground reactor; oil quality; power factor; power transformer maintenance; protection equipment; radiator; regulating PT; surge arrester; thermo scan; transformer control cabinet; Insulators; Maintenance engineering; Oil insulation; Power transformer insulation; Reactive power; Testing; health index of power transformer; power transformer condition;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering and Automation Conference (PEAM), 2012 IEEE
Conference_Location
Wuhan
Print_ISBN
978-1-4577-1599-0
Type
conf
DOI
10.1109/PEAM.2012.6612413
Filename
6612413
Link To Document