• DocumentCode
    3234729
  • Title

    Investigation of corona phenomenon for a reduced-scale model of hybrid AC and DC lines

  • Author

    Metwally, I.A.

  • Author_Institution
    Dept. of Electr. Eng., Mansoura Univ., Egypt
  • Volume
    2
  • fYear
    1996
  • fDate
    20-23 Oct 1996
  • Firstpage
    610
  • Abstract
    A reduced-scale model of a single-phase ac (50 Hz) and a unipolar dc was developed with a suitable scaling factor where the applied voltages were varied up to 80 kV. Many factors were examined to show their effects on the I-V characteristics and on the corona current oscillograms. Also, a two-dimensional field computation program based on the charge simulation method (CSM) was used to model both the hybrid analog and an ac 132 kV double-circuit transmission lines in order to compute the ground-level electric field, number of streamers (for a constant time duration) and corona inception voltage for different arrangements and energization types and levels
  • Keywords
    corona; electric fields; oscillographs; power transmission lines; 132 kV; 50 Hz; I-V characteristics; charge simulation method; corona phenomenon; current oscillograms; double-circuit transmission lines; energization types; ground-level electric field; hybrid AC/DC lines; inception voltage; reduced-scale model; streamers; two-dimensional field computation; Analog computers; Circuits; Computational modeling; Conductors; Corona; Electric fields; Poles and towers; Surges; Transformers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1996., IEEE 1996 Annual Report of the Conference on
  • Conference_Location
    Millbrae, CA
  • Print_ISBN
    0-7803-3580-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.1996.564544
  • Filename
    564544