Capacity performance tests were completed on 47 flooded lead-calcium batteries ranging from 5- to 23-years-old. These batteries had been maintained in the Minuteman missile silos on float charge over the majority of their life to provide emergency or secondary power. Capacity results showed no capacity degradation in the oldest batteries and cell dissections revealed only minor deterioration of the lead calcium grids. However, an increase in the cell float voltage range was observed in the 22-year-old batteries. Although signs of deterioration have begun, the solid capacity results indicate additional service life is still available. Additional data is also presented from on-going cycle tests being performed on a 5-and 21-year-old battery which supports the performance capability remaining in these aged batteries
Keywords
calcium; lead; life testing; military equipment; power supplies to apparatus; secondary cells; 5 to 23 y; Minuteman launch facility; Minuteman missile silos; Pb-Ca flooded batteries; PbCa; battery testing; capacity performance tests; cell dissections; cell float voltage; cycle tests; emergency power; float charge; flooded lead acid batteries; lead calcium grids; performance capability; secondary power; service life projection; Batteries; Calcium; Degradation; Life testing; Manufacturing; Missiles; Performance evaluation; Space technology; System testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Battery Conference on Applications and Advances, 1996., Eleventh Annual
Conference_Location
Long Beach, CA
Print_ISBN
0-7803-2994-5
Type
conf
DOI
10.1109/BCAA.1996.484976
Filename
484976
Link To Document