On the corona voltage-current characteristic of unipolar HVDC transmission lines
Author :
Li, Xin ; Raghuveer, M.R. ; Ciric, I.R.
Author_Institution :
Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
Volume :
2
fYear :
1996
fDate :
20-23 Oct 1996
Firstpage :
654
Abstract :
Simplified analytical analysis of ionized fields associated with HVDC transmission lines is possible if it is based on Deutsch´s assumption. The resulting voltage-current (V-I) characteristic may be conveniently used to calculate the power losses of a HVDC transmission line. However, such an approach has been criticized because Deutsch´s assumption is considered invalid for the line-plane geometry. This paper verifies the validity of the V-I characteristic thus obtained by comparing it with numerical results which are generated using a new method developed by the authors, in which Deutsch´s assumption is not employed
Keywords :
HVDC power transmission; corona; electric fields; losses; space charge; corona voltage-current characteristic; ionized fields; line-plane geometry; power losses; unipolar HVDC transmission lines; Character generation; Conductors; Corona; Equations; Geometry; HVDC transmission; Propagation losses; Space charge; Voltage; Wind energy generation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1996., IEEE 1996 Annual Report of the Conference on
Conference_Location :
Millbrae, CA
Print_ISBN :
0-7803-3580-5
Type :
conf
DOI :
10.1109/CEIDP.1996.564555