DocumentCode
3238846
Title
Defective insulators in live working on a 550 kV compact steel lattice tower
Author
Gela, G. ; Kientz, H. ; Fox, H.J., Jr ; Mitchell, J.D. ; Lyons, P.F.
Author_Institution
EPRI Power Delivery Centre, Lenox, MA, USA
fYear
1995
fDate
29 Oct-3 Nov 1995
Firstpage
150
Lastpage
155
Abstract
Research was conducted to determine the minimum number of healthy insulator units needed to ensure worker safety in live working on a compact 550 kV steel lattice tower. A large variety of worksite conditions was investigated. Test results confirm the conservative nature of the CIGRE formula for defective insulator units, and modifications to the formula are suggested, The recommended number of healthy units is 12 in a string of 24 units for the case of live work on a compact 550 kV tower, when the portable protective gap (PPG) is used. Adjustment for altitude should be made above 900 m (3000 ft.)
Keywords
health hazards; insulators; maintenance engineering; poles and towers; safety; steel; 550 kV; CIGRE formula; altitude adjustment; compact steel lattice tower; defective insulators; insulator flashover; live working; portable protective gap; worker safety; Flashover; Health and safety; Insulation; Lattices; Occupational stress; Poles and towers; Protection; Steel; Surges; Voltage;