• DocumentCode
    3238846
  • Title

    Defective insulators in live working on a 550 kV compact steel lattice tower

  • Author

    Gela, G. ; Kientz, H. ; Fox, H.J., Jr ; Mitchell, J.D. ; Lyons, P.F.

  • Author_Institution
    EPRI Power Delivery Centre, Lenox, MA, USA
  • fYear
    1995
  • fDate
    29 Oct-3 Nov 1995
  • Firstpage
    150
  • Lastpage
    155
  • Abstract
    Research was conducted to determine the minimum number of healthy insulator units needed to ensure worker safety in live working on a compact 550 kV steel lattice tower. A large variety of worksite conditions was investigated. Test results confirm the conservative nature of the CIGRE formula for defective insulator units, and modifications to the formula are suggested, The recommended number of healthy units is 12 in a string of 24 units for the case of live work on a compact 550 kV tower, when the portable protective gap (PPG) is used. Adjustment for altitude should be made above 900 m (3000 ft.)
  • Keywords
    health hazards; insulators; maintenance engineering; poles and towers; safety; steel; 550 kV; CIGRE formula; altitude adjustment; compact steel lattice tower; defective insulators; insulator flashover; live working; portable protective gap; worker safety; Flashover; Health and safety; Insulation; Lattices; Occupational stress; Poles and towers; Protection; Steel; Surges; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Construction and Live Line Maintenance, 1995. ESMO-95 Proceedings., Seventh International Conference on
  • Conference_Location
    Columbus, OH
  • Print_ISBN
    0-7803-2506-0
  • Type

    conf

  • DOI
    10.1109/TDCLLM.1995.485050
  • Filename
    485050