DocumentCode
3239048
Title
Minimum approach distances in hotline work a practical method for their determination
Author
Iglesias, L.G.
Author_Institution
Compania Sevillana de Electricidad
fYear
1995
fDate
29 Oct-3 Nov 1995
Firstpage
219
Lastpage
228
Abstract
The authors intend to establish, for each voltage value and not for each voltage bracket, two minimum approach distances for hot-line power transmission line maintenance which, as discussed in this paper, correspond to points, on two converging straight lines which cover virtually all clearances used in various countries and are highly consistent with the studies performed by the WG 10 of IEC/TC 78. It may be useful in practice to use one of these extreme clearances or some other intermediate value depending an the climate conditions; thus, for example, for relative humidity over 80% the maximum clearance distance would be taken: and for relative humidity under 20% the minimum clearance distance would be taken. It is likewise intended to separate the inadvertent movement distances and that these be taken into account as one of the parameters coming into the sum for all determinations of minimum approach distances, since said inadvertent movement dimensions are susceptible to variation with improvements in technology and work procedures. Furthermore, since they always come into the sum, one has to be careful that these inadvertent movement distances cannot be left out or added twice
Keywords
maintenance engineering; personnel; power overhead lines; power transmission lines; safety; climate conditions; hot-line maintenance; inadvertent movement; minimum approach distances; minimum clearance distance; overhead power transmission lines; relative humidity; work procedures; Air safety; Humidity; IEC standards; Notice of Violation; Proposals; USA Councils; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Construction and Live Line Maintenance, 1995. ESMO-95 Proceedings., Seventh International Conference on
Conference_Location
Columbus, OH
Print_ISBN
0-7803-2506-0
Type
conf
DOI
10.1109/TDCLLM.1995.485060
Filename
485060
Link To Document