DocumentCode :
3239241
Title :
Optimization research for horizontal spacing of no-duct inducing fan system
Author :
Xing, Jincheng ; Wang, Yanqin ; Li, Jianxing ; Ling, Jihong ; Lin, Guozhen
Author_Institution :
Sch. of Environ. Sci. & Technol., Tianjin Univ., Tianjin, China
fYear :
2011
fDate :
22-24 April 2011
Firstpage :
4253
Lastpage :
4256
Abstract :
For the problem of reasonable longitudinal and horizontal spacing of inducing fan in ventilation system in underground garages, the test of single inducing fan was carried out. Comparing the results of the test and of the numerical simulation, boundary conditions of numerical simulation were determined. By using fluent software, appropriate longitudinal spacing of inducing fan was gotten. Thinking of the poly trope of volume capacity ratio and parking utilization factor, the concept of garage utilization coefficient was defined. On this basis, CO concentration is taken as control standard in this paper and numerical simulation is performed for kinds of small space models. As a result, we get the recommended values of reasonable horizontal spacing for inducing fans´ arrangement. Reference data are given for the design of no-duct inducing fan system of underground parking garages in future.
Keywords :
fans; geotechnical engineering; numerical analysis; optimisation; structural engineering; ventilation; Fluent software; garage utilization coefficient; no-duct inducing fan system; numerical simulation; optimization; underground parking garages; ventilation system; Architecture; Buildings; Carbon; Computer architecture; Numerical simulation; Space technology; Ventilation; CO concentration; horizontal spacing; inducing fan; longitudinal spacing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Technology and Civil Engineering (ICETCE), 2011 International Conference on
Conference_Location :
Lushan
Print_ISBN :
978-1-4577-0289-1
Type :
conf
DOI :
10.1109/ICETCE.2011.5775381
Filename :
5775381