Title :
Permittivity matching effects on coil section of oil-immersed transformer
Author :
Hikosaka, T. ; Asada, T. ; Miyamoto, M. ; Kousaka, M.
Author_Institution :
Lab. of Power Technol., Fuji Electr. Corp. Res. & Dev. Ltd., Chiba, Japan
fYear :
1999
fDate :
1999
Firstpage :
499
Lastpage :
502
Abstract :
The lightning impulse breakdown voltage of the coil section of oil-immersed transformers is dominated by the partial discharge voltage of the wedge-shaped oil gaps made of the paper insulated conductors, mineral oil, and the coil section spacers. We have studied the permittivity matching effects on the lightning impulse breakdown voltage of the coil section models by means of the experiments and the electric field analyses. The relationship between the critical electric field E in the wedge-shaped oil gap when the breakdown occurred, and the gap length d was acquired. Moreover, the breakdown strength of the coil section models were estimated by using the above relationship within 6% error compared to the measured average values
Keywords :
electric breakdown; partial discharges; permittivity; transformer oil; transformers; coil section; coil section spacers; critical electric field; gap length; lightning impulse breakdown voltage; mineral oil; oil-immersed transformer; paper insulated conductors; partial discharge voltage; permittivity matching; wedge-shaped oil gaps; Breakdown voltage; Coils; Conductors; Electric breakdown; Lightning; Oil insulation; Partial discharges; Permittivity; Petroleum; Power transformer insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Dielectric Liquids, 1999. (ICDL '99) Proceedings of the 1999 IEEE 13th International Conference on
Conference_Location :
Nara
Print_ISBN :
0-7803-4759-5
Type :
conf
DOI :
10.1109/ICDL.1999.798981
Filename :
798981
Link To Document :