DocumentCode :
3245762
Title :
Corona defection for OF cable and oil reactor on running by loop antenna
Author :
Higuchi, Takemitsu
Author_Institution :
Res. Center, Kansai Electr. Power Co. Inc., Hyogo, Japan
fYear :
1999
fDate :
1999
Firstpage :
537
Lastpage :
540
Abstract :
The author attempts to detect the corona pulse that occurs inside the power shunt-reactor and power cable at an early stage of insulation degeneration with an outside loop antenna. The principle of the method is described and the technique is applied to the case of corona pulse measurement caused by a partial discharge inside a shunt-reactor. Frequency spectra of the detected pulses are presented. A second example involves measurement of corona pulse from 77 kV OF cable
Keywords :
corona; insulating oils; insulation testing; loop antennas; partial discharge measurement; power cable insulation; power cable testing; pulse measurement; saturable core reactors; 154 kV; 20 to 50 MHz; 77 kV; OF cable; corona pulse detection; frequency spectra; insulation degeneration; oil reactor; outside loop antenna; partial discharge; power cable; power shunt-reactor; Antenna measurements; Cable insulation; Corona; Frequency; Inductors; Oil filled cables; Partial discharges; Petroleum; Power cables; Pulse measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Dielectric Liquids, 1999. (ICDL '99) Proceedings of the 1999 IEEE 13th International Conference on
Conference_Location :
Nara
Print_ISBN :
0-7803-4759-5
Type :
conf
DOI :
10.1109/ICDL.1999.798990
Filename :
798990