DocumentCode :
3248667
Title :
Review of 20 kV Overhead Distribution Lines Reliability Against Lightning at PLN APJ Bogor
Author :
Zoro, R. ; Mefiardhi, R. ; Rosidin, A. ; Poerwanto, E.
Author_Institution :
Sch. of Electr. Eng. & Informatics, Inst. of Technol., Bandung
fYear :
2006
fDate :
38869
Firstpage :
455
Lastpage :
459
Abstract :
Because the low insulation strength of distribution lines, virtually all strokes that terminate on the phase conductors of a distribution lines will result in flashover. However, in some cases, shield wire may provide some measure of protection from these direct strokes. Distribution lines are also subjected to over voltages induced by strokes that terminate adjacent to the line. In fact, most of the flashovers that occur are cause by these induced voltages. This paper gives a review on existing condition on unimproved distribution lines in Bogor and some improvement that has to be made. Bogor is well known as a highest lightning activity area in Indonesia, with over 300 thunderstorm days a year
Keywords :
flashover; overvoltage protection; power distribution protection; power distribution reliability; power overhead lines; thunderstorms; 20 kV; Indonesia; PLN APJ Bogor; flashover; lightning; low insulation strength; over voltage; overhead distribution lines reliability; phase conductor; thunderstorm; Breakdown voltage; Conductors; Dielectrics and electrical insulation; Flashover; Lightning; Power distribution lines; Protection; Solids; Voltage control; Wire; critical flashover voltage (CFO); flashover rate; line insulator; outages cause by lightning;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and applications of Dielectric Materials, 2006. 8th International Conference on
Conference_Location :
Bali
Print_ISBN :
1-4244-0189-5
Electronic_ISBN :
1-4244-0190-9
Type :
conf
DOI :
10.1109/ICPADM.2006.284213
Filename :
4062702
Link To Document :
بازگشت