• DocumentCode
    3249761
  • Title

    Validation of single frequency Z measurement for standby battery state of health determination

  • Author

    Kiel, Martin ; Sauer, Dirk Uwe ; Turpin, Pierre ; Naveed, Mohamed ; Favre, Eric

  • Author_Institution
    Electrochem. Energy Conversion & Storage Syst. Group, RWTH Aachen Univ., Aachen
  • fYear
    2008
  • fDate
    14-18 Sept. 2008
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    Impedance has been discussed for a long time as an indicator for the state of health (SOH) of lead-acid batteries for standby applications such as UPS systems. The research contains the analysis of the relation between capacity and impedance measurement at different frequencies. Several batteries of different manufacturers and capacity were aged systematically and the impedance measurements were done under similar conditions as in real UPS systems. Impedance measurements with the low cost device and full scale laboratory equipment and capacity tests have been performed periodically.
  • Keywords
    electric impedance measurement; power system measurement; uninterruptible power supplies; impedance measurement; power system monitoring; standby battery; state of health determination; uninterruptible power supplies; Aging; Battery charge measurement; Costs; Frequency measurement; Impedance measurement; Laboratories; Manufacturing; Performance evaluation; Testing; Uninterruptible power systems; Battery storage plants; Impedance Spectroscopy; Power system monitoring; SOH determination;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2008. INTELEC 2008. IEEE 30th International
  • Conference_Location
    San Diego, CA
  • Print_ISBN
    978-1-4244-2055-1
  • Electronic_ISBN
    978-1-4244-2056-8
  • Type

    conf

  • DOI
    10.1109/INTLEC.2008.4664020
  • Filename
    4664020