• DocumentCode
    3250530
  • Title

    Energy saving active cooling systems for outdoor cabinet

  • Author

    Yuping, Hong ; Shengqin, Ji ; Yunhui, Zhang ; Xiaoming, Kong ; Qiao, Chen ; Cucchietti, Flavia ; Griffa, Gianluca

  • Author_Institution
    Huawei Technol. Co., Ltd., Shenzhen
  • fYear
    2008
  • fDate
    14-18 Sept. 2008
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Currently the energy-saving strategy is one of the top priorities of Telecom Operators and Governments. In particular, the area of cooling has heavy impact on the total electrical energy consumption, and needs to be optimized to improve overall performances, reducing both CAPEX/OPEX and the environmental impact. In this paper, two innovative cooling solutions for outdoor cabinets are described: free cooling system and manhole cooling system. Free cooling system is a solution directly using external fresh air in order to increase the cooling efficiency of active outdoor cabinet. Three key technologies are developed and used in this system: experimental results indicate that excellent heat dissipation capacity and good corrosion resistance of outdoor cabinet are achieved simultaneously. Manhole cooling system is another innovative solution, in which manhole (part of the underground maintenance infrastructure of TLC operator) is innovatively used as a huge heat sink. The cooling performance of manhole cooling system is predicted through CFD simulations. It has been demonstrated that as much as 60% of the heat load can be dissipated into the ground, still maintaining the equipment well within its operating temperature range. The proposed cooling solutions are particularly interesting for the FTTCab architecture. FTTCab deployment, as foreseen in several NGN strategies, will strongly increase in the next years.
  • Keywords
    air conditioning; computational fluid dynamics; heat sinks; power consumption; CFD simulations; electrical energy consumption; energy saving active cooling systems; energy-saving strategy; environmental impact; free cooling system; heat load; heat sink; innovative cooling solutions; manhole cooling system; outdoor cabinet; Computational fluid dynamics; Cooling; Corrosion; Energy consumption; Government; Heat sinks; Land surface temperature; Predictive models; Resistance heating; Telecommunications;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2008. INTELEC 2008. IEEE 30th International
  • Conference_Location
    San Diego, CA
  • Print_ISBN
    978-1-4244-2055-1
  • Electronic_ISBN
    978-1-4244-2056-8
  • Type

    conf

  • DOI
    10.1109/INTLEC.2008.4664063
  • Filename
    4664063