DocumentCode :
3251153
Title :
Water hammer protection in water supply system: A new approach with practical implementation
Author :
Roy, J.K. ; Roy, P.K. ; Basak, P.
Author_Institution :
Dean-Res., Narula Inst. of Technol., Kolkata, India
fYear :
2011
fDate :
26-28 Dec. 2011
Firstpage :
1
Lastpage :
6
Abstract :
An unprotected water pipe mainly suffers frequent damages due to water hammer surges developed inside the pipe lines. This paper studied the effect of water hammer in a water delivery pipe theoretically and developed a novel method to combat the damage. The Public Health Engineering Directorate, Government of West Bengal, India has set up an arsenic area piped water supply scheme in the year 2003 in South 24 Pgs, West Bengal, where about 320Km length of water mains have been laid to supply arsenic free drinking water to the arsenic affected consumers. It was suffering from frequent ruptures of pipe joints and its weaker portions due to water hammer surges. From the result of theoretical studies a novel method has been developed and implemented in this water supply scheme to combat the situation. The project is consisting of a smart electronic pressure transmitter, PLC based SCADA system and valve automation. The method of measurement of surge pressure at the header end of the water mains and the method of bypassing some part of water from water mains back to the water storage are used in this technique. This method absorbs sudden surge developed due to water hammering inside the pipe and thus maintains surge free water supply at a desired pressure. The Zero Failure rates of the water mains are observed after the installation of this technique. One installation per two ground water storage connected with water mains of maximum length 32Km is suggested.
Keywords :
SCADA systems; arsenic; health and safety; pipelines; programmable controllers; water supply; India; PLC based SCADA system; Public Health Engineering Directorate; West Bengal; arsenic area piped water supply scheme; pipelines; smart electronic pressure transmitter; unprotected water pipe; water hammer protection; water supply system; zero failure rates; Materials; Monitoring; Reservoirs; Surge protection; Surges; Valves; Arsenic area water supply scheme; Joukowsky equation; PLC; SCADA; Water hammer;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Communication and Industrial Application (ICCIA), 2011 International Conference on
Conference_Location :
Kolkata, West Bengal
Print_ISBN :
978-1-4577-1915-8
Type :
conf
DOI :
10.1109/ICCIndA.2011.6146652