Electrical Switching Life of Vacuum Circuit Breaker Interrupters
Author :
Slade, Paul G. ; Smith, R. Kirkland
Author_Institution :
Vacuum Interrupter Technol. Eaton Electr. Horseheads, Horseheads, NY
fYear :
2006
fDate :
25-27 Sept. 2006
Firstpage :
32
Lastpage :
37
Abstract :
Experiments were performed to determine the electrical life of a vacuum interrupter as a function of current. The test currents ranged from the normal load currents of 630 A (rms) to 3150 A (rms) to higher currents of 20% to 100% of the rated short-circuit current. The two vacuum interrupter contact styles were evaluated: the transverse magnetic field (TMF) contact and the axial magnetic field structure (AMF). For the short-circuit current switching the AMF contact shows a longer electrical life, but the erosion may not be the only limitation on the life of the vacuum interrupter. The results will be discussed in terms of the expected performance of the two contact designs and on the operating life of a vacuum interrupter.
Keywords :
electrical contacts; life testing; short-circuit currents; vacuum circuit breakers; vacuum interrupters; axial magnetic field structure; current 630 A to 3150 A; electrical switching life; erosion; short-circuit current switching; transverse magnetic field contact; vacuum circuit breaker interrupter; Anodes; Cathodes; Circuit breakers; Circuit testing; Contacts; Interrupters; Magnetic fields; Switching circuits; Vacuum arcs; Vacuum technology; arcing erosion of contacts; component; electrical switching life; vacuum interrupters;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical contacts - 2006, proceedings of the fifty-second ieee holm conference on
Conference_Location :
Montreal, QC
Print_ISBN :
1-4244-0581-5
Type :
conf
DOI :
10.1109/HOLM.2006.284061
Filename :
4063097
Link To Document :
بازگشت