DocumentCode :
3255989
Title :
Determination of the Best Closing Phase Angle for AC Contactor Based on Game Theory
Author :
Xiuping, Su ; Jianguo, Lu ; Bingjun, Gao ; Guojin, Liu ; Wenhua, Li
Author_Institution :
Electr. Apparatus Inst., Hebei Univ. of Technol., Tianjin
fYear :
2006
fDate :
25-27 Sept. 2006
Firstpage :
188
Lastpage :
192
Abstract :
Any contactor bounce is undesirable since this causes arcing which shortens the life of the contacts when contacts close. The rebounds and the closing speeds are different with the closing phase angle of the electromagnetic coil voltage switching on when contactors close. This paper discussed the determination of the best closing phase angle of the electromagnetic coil voltage switching on. Taking closing phase angle as optimization variable, the closing velocities of three phase contacts and armature as objectives, and taking moving velocities lower than their worst values as restrictions, the optimization model was established. Game theory was introduced and adopted to solve the multi-objectives optimization problem. Taking CJ20 AC contactor as an example, the best closing phase angle was determined by combing the calculating and testing results.
Keywords :
coils; contactors; game theory; CJ20 AC contactor; arcing; closing phase angle; contactor bounce; electromagnetic coil voltage switching; game theory; multi-objectives optimization problem; AC motors; Coils; Contacts; Electronic circuits; Electronic mail; Game theory; Optimization methods; Phase measurement; Testing; Voltage; AC contactor; game theory; optimization; the best closing phase angle;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical contacts - 2006, proceedings of the fifty-second ieee holm conference on
Conference_Location :
Montreal, QC
Print_ISBN :
1-4244-0581-5
Type :
conf
DOI :
10.1109/HOLM.2006.284085
Filename :
4063121
Link To Document :
بازگشت