DocumentCode :
3257420
Title :
Soft Transition Operation of UPS in High-Power-Factor Mode of Three-Phase Front-End Rectifier
Author :
Dhomane, G.A. ; Suryawanshi, H.M.
Author_Institution :
VNIT, Nagpur
fYear :
2007
fDate :
27-30 Nov. 2007
Firstpage :
1431
Lastpage :
1435
Abstract :
A three-phase to single-phase ac-to-ac converter, with soft-transition of switches is presented. The converter has THD less than 4% and operates at almost unity-power-factor for wide variations in load, due to high frequency current injection, at the input of front-end- rectifier. A small filter is required at the output for filtering the high-frequency content. Sinusoidal PWM technique is used for controlling the output voltage. DSP is used for generating the desired gate pulses. The converter has high efficiency, low EMI emissions, high power packing density and suitable for UPS system. A Simulation and experimentation is carried out on a 3 kW converter and experimental results are in good agreement with simulation results.
Keywords :
AC-AC power convertors; PWM rectifiers; digital signal processing chips; power factor; power filters; uninterruptible power supplies; voltage control; DSP; UPS soft transition operation; high frequency current injection; high power packing density; high-power-factor mode; single-phase AC-to-AC converter; sinusoidal PWM technique; three-phase front-end rectifier; voltage control; Digital signal processing; Filtering; Filters; Frequency conversion; Pulse width modulation; Rectifiers; Switches; Switching converters; Uninterruptible power systems; Voltage control; High-frequency-current-injection; High-power-factor; Power-factor-correction circuit; Soft-transition;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics and Drive Systems, 2007. PEDS '07. 7th International Conference on
Conference_Location :
Bangkok
Print_ISBN :
978-1-4244-0645-6
Electronic_ISBN :
978-1-4244-0645-6
Type :
conf
DOI :
10.1109/PEDS.2007.4487892
Filename :
4487892
Link To Document :
بازگشت