    Acid aging of silicone rubber housing for polymer insulators

  • Author

    Umeda, Itsuki ; Tanaka, Kenji ; Kondo, Takanori ; Kondo, Kuniaki ; Suzuki, Yoshihiro

  • Author_Institution
    NGK Insulators, Ltd., Komaki
  • fYear
    2008
  • fDate
    7-11 Sept. 2008
  • Firstpage
    518
  • Lastpage
    521
  • Abstract
    An aged silicone polymer insulator, which had been used at testing station near sea coast for approx. 10 years, was investigated. The aging mode was different from erosion. It was confirmed that the rubber aging phenomena was similar to damage due to nitric acid by FT-IR analysis. It is deemed that the acid was generated during corona discharge on rubber housing. In order to avoid such a rubber aging, it is important to minimize corona discharge even under wet conditions.
  • Keywords
    Fourier transform spectra; ageing; corona; infrared spectra; silicone rubber; FT-IR analysis; acid aging; corona discharge; nitric acid; silicone polymer insulator; silicone rubber housing; testing station; Aging; Dielectrics and electrical insulation; Insulator testing; Organic materials; Plastic insulation; Pollution measurement; Polymers; Rubber; Stress; Surface contamination;