Title :
Determination of wind speed value in calculation of supply air volume
Author_Institution :
Dept. of Fire Protection Eng., Chinese People´s Armed Police Force Acad., Langfang, China
Abstract :
Using the method of mechanical air supply can protect the escape route against smoke. The wind speed method is one of the most commonly used methods in determining the supply air volume. The average value of supply wind velocity v in the calculation parameters of wind speed method has been studied using numerical simulation method in this paper. The results show that at natural smoke venting, when the building is protected with sprinkler system, the value of v should take 0.7m/s, otherwise the value of v should take 0.9m/s.
Keywords :
aerodynamics; numerical analysis; smoke; structural engineering; ventilation; wind; building escape route; mechanical air supply; natural smoke venting; smoke control; sprinkler system; supply air volume calculation; supply wind velocity; wind speed value determination; Atmospheric modeling; Buildings; Fires; Heating; Presses; Temperature distribution; Wind speed; FDS; mechanical pressurized air supply; numerical simulation; wind speed;
Conference_Titel :
Emergency Management and Management Sciences (ICEMMS), 2011 2nd IEEE International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9665-5
DOI :
10.1109/ICEMMS.2011.6015668