Title :
Characteristics of on-line and off-line partial discharge for hydrogenerator stator windings with AE sensor and CT sensor
Author :
Maeda, I. ; Kaneko, T. ; Takenouchi, O. ; Miyake, T. ; Sakoda, T. ; Otsubo, M. ; Fukumoto, S. ; Tokumitsu, A. ; Kai, T. ; Ando, M.
Author_Institution :
Univ. of Miyazaki, Miyazaki
fYear :
2008
fDate :
7-11 Sept. 2008
Firstpage :
577
Lastpage :
580
Abstract :
We pay attention to an insulation diagnosis technique of on-line hydrogenerator stator windings. On-line partial discharge monitoring and diagnosis of the insulation of hydrogenerator machines can be expected to reduce their maintenance costs. Therefore, we aim at development of the hybrid diagnostic method that ultrasonic wave signal occurring by partial discharge and leakage current flowing through neutral grounding cable of hydrogenerator. We set up many AE (acoustic emission) sensors to stator core and set up a CT (current transformer) sensor at neutral grounding cable of hydrogenerator. We measured AE signal and neutral grounding cable leakage current of hydrogenerator on stream. Furthermore, we set up measurement equipment in a hydrogenerator wing channel and measured AE signal and leakage current flowing at neutral grounding cable by partial discharge for a long term. In this paper, we have measured the relationship of on-line hydrogenerator out put and AE signal and leakage current flowing at neutral grounding cable. And, we have measured the AE signal and leakage current on the dielectric loss tangent test and partial discharge pulse at off-line test.
Keywords :
acoustic emission; cables (electric); current transformers; earthing; hydroelectric generators; leakage currents; partial discharges; stators; acoustic emission sensor; current transformer sensor; dielectric loss tangent test; hybrid diagnostic method; hydrogenerator stator windings; hydrogenerator wing channel; insulation diagnosis; leakage current; neutral grounding cable; partial discharge; ultrasonic wave signal; Acoustic measurements; Current measurement; Current transformers; Dielectric loss measurement; Grounding; Leakage current; Partial discharge measurement; Partial discharges; Sensor phenomena and characterization; Stator windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
Conference_Location :
Mie
Print_ISBN :
978-4-88686-005-7
Electronic_ISBN :
978-4-88686-006-4
Type :
conf
DOI :
10.1109/ISEIM.2008.4664533
Filename :
4664533
Link To Document :
بازگشت