Title :
Interconnection of two micro hydro units forming a mini-grid system using soft connection
Author :
Adhikary, B. ; Ghimire, B. ; Karki, P.
Author_Institution :
Dept. of Electr. & Electron. Eng., Kathmandu Univ., Kathmandu, Nepal
Abstract :
This paper presents the soft connection between two micro-hydro units forming a mini-grid system. It describes the operation and the design of the induction generator controller (IGC), used for the power balancing at varying consumers load as required for standalone micro-hydro generators and the synchronizer unit, used for the mini-grid interconnection. Three phase induction motors are used as single phase generators by using C-2C capacitor configuration for supplying single phase resistive load. This paper proposes a simple soft connection scheme based on classical zero crossing detector. Operation and experimental tests of IGC based mini-grid system with soft connection is also presented. Through the results it has been shown that the proposed model is feasible for rural electrification schemes.
Keywords :
asynchronous generators; distributed power generation; hydroelectric generators; hydroelectric power stations; induction motors; power system interconnection; C-2C capacitor configuration; classical zero crossing detector; induction generator controller; microhydro unit interconnection; minigrid system interconnection; phase induction motors; power balancing; rural electrification schemes; single phase generators; single phase resistive load; standalone microhydro generators; synchronizer unit; Frequency synchronization; Induction generators; Induction motors; Inverters; Microhydro power; Power generation; Power system interconnection; Power system protection; Power system transients; Stress; Ballast load; Induction generator; Induction generator controller (IGC); Minigrid; Standalone system; Synchronizer unit;
Conference_Titel :
TENCON 2009 - 2009 IEEE Region 10 Conference
Conference_Location :
Singapore
Print_ISBN :
978-1-4244-4546-2
Electronic_ISBN :
978-1-4244-4547-9
DOI :
10.1109/TENCON.2009.5396207