Correlation between light emission intensity and partial discharge magnitude in voids
Author :
Sun, Changhao ; Meng, Yongpeng ; Guo, Zide ; Gao, Minggang ; Wu, Kai
Author_Institution :
State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an
fYear :
2008
fDate :
7-11 Sept. 2008
Firstpage :
436
Lastpage :
439
Abstract :
Light-emission of partial discharge (PD) was measured by photo multiplication tube (PMT) under AC voltage and simultaneously partial discharge magnitude was measured. Investigation of the correlation between them shows that the intensity of light emission is in proportion to PD magnitude but the ratio between them changes slightly with the aging time. Different voids were tested to study the influence of thickness and diameter on the correlation. This report provides a foundation for the further study of PD under voltage surges.
Keywords :
insulation testing; materials testing; partial discharge measurement; photomultipliers; voids (solid); AC voltage; aging time; diameter influence; light emission intensity; partial discharge magnitude measurement; photo multiplication tube; thickness influence; void testing; voltage surge; Aging; Dielectrics and electrical insulation; Electric variables measurement; Electron tubes; Partial discharge measurement; Partial discharges; Power measurement; Surges; Testing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
Conference_Location :
Mie
Print_ISBN :
978-4-88686-005-7
Electronic_ISBN :
978-4-88686-006-4
Type :
conf
DOI :
10.1109/ISEIM.2008.4664579
Filename :
4664579
Link To Document :
بازگشت