Abstract :
Partial discharge is a well known phenomenon that caused insulation degradation in cross-linked polyethylene power cable. Thus eventually will cause insulation failure. When partial discharge occurs, it radiates electromagnetic field in all direction. This electromagnetic field has a bandwidth of about 1 GHz at source. This paper hence describes the design of a simple single layer air-core coil as inductive probe to detect the presence of magnetic field components due to partial discharge. It is shown that, it is possible to detect the presence of PD at 1 m away from the cable.
Keywords :
XLPE insulation; electromagnetic fields; partial discharges; power cables; probes; XLPE cable; bandwidth 1 GHz; cross-linked polyethylene power cable; distance 1 m; electromagnetic field; inductive probe; insulation degradation; insulation failure; magnetic field detection; partial discharge signal; single layer air-core coil; Bandwidth; Cable insulation; Coils; Degradation; Electromagnetic fields; Magnetic fields; Partial discharges; Polyethylene; Power cables; Probes;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
Conference_Location :
Mie
Print_ISBN :
978-4-88686-005-7
Electronic_ISBN :
978-4-88686-006-4
Type :
conf
DOI :
10.1109/ISEIM.2008.4664581
Filename :
4664581
Link To Document :
بازگشت