• DocumentCode
    3259924
  • Title

    A method of temperature calculation of power cable conductor

  • Author

    Yang, Wenhu ; Liu, Ying ; Xu, Yang ; Cao, Xiaolong ; Li, Ji ; Xu, Man

  • Author_Institution
    State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an
  • fYear
    2008
  • fDate
    7-11 Sept. 2008
  • Firstpage
    460
  • Lastpage
    462
  • Abstract
    More and more distributed temperature systems were applied in high voltage cable insulation online monitoring, which make it possible to calculate the conductor temperature accurately and estimate the true carrying capacity of power cable. Applying the mathematics model of heat network, this paper propose a method to calculate conductor temperature from temperature of cable outer sheath, the structure and laying conditions of power cable should be given certainly. Factors that may have effect on the result calculated were also discussed. The test carried out at Cable Research Institute prove that temperature difference of cable conductor between measured on field and calculated by this method can be controlled in 3 K.
  • Keywords
    power cable insulation; conductor temperature; distributed temperature systems; heat network; high voltage cable insulation online monitoring; mathematics model; power cable conductor; Cable insulation; Cable shielding; Conductors; Mathematical model; Mathematics; Power cables; Power system modeling; Temperature; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
  • Conference_Location
    Mie
  • Print_ISBN
    978-4-88686-005-7
  • Electronic_ISBN
    978-4-88686-006-4
  • Type

    conf

  • DOI
    10.1109/ISEIM.2008.4664586
  • Filename