• DocumentCode
    3260343
  • Title

    Assessment of transformer insulation condition by evaluation of paper-oil system

  • Author

    Murthy, T.S.R.

  • Author_Institution
    Corp. Res. & Dev. Div., Bharat Heavy Electr. Ltd., Hyderabad, India
  • Volume
    1
  • fYear
    1996
  • fDate
    20-23 Oct 1996
  • Firstpage
    332
  • Abstract
    Cellulose paper is the best known solid insulating material used in transformers. It is exposed to different types of stresses under normal/abnormal service conditions. This leads to ageing of the paper, causing depolymerisation of the cellulose material and the formation of decomposition products, like 2-furfuraldehyde and 5-hydroxymethyl, which dissolve in oil. Degradation of paper causes a reduction in the degree of polymerisation. Hence, the chemical analysis of transformer oil and paper gives evidence of changes that are taking place in the winding insulation during the service condition of the transformer. The author discusses the degree of polymerisation of fresh and service aged cellulose paper samples and analyses the oil samples, using HPLC, collected from different site transformers. The oxidation stability of oil samples was determined by RBOT and the insulation condition was assessed taking into consideration the experimental and theoretical furfural values. The condition of cellulose paper was also assessed by SEM
  • Keywords
    ageing; chromatography; dissociation; insulation testing; oxidation; paper; power transformer insulation; power transformer testing; scanning electron microscopy; transformer oil; 2-furfuraldehyde; 5-hydroxymethyl; HPLC; SEM; ageing; cellulose depolymerisation; cellulose paper; chemical analysis; decomposition products; degree of polymerisation; furfural content; oxidation stability; paper degradation; paper-oil system; rotating bomb oxidation test; service conditions; transformer insulation condition assessment; transformer oil; winding insulation; Aging; Chemical analysis; Oil insulation; Oxidation; Petroleum; Polymers; Power transformer insulation; Solids; Stress; Thermal degradation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1996., IEEE 1996 Annual Report of the Conference on
  • Conference_Location
    Millbrae, CA
  • Print_ISBN
    0-7803-3580-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.1996.564696
  • Filename