Differentiation of faults from power swings and detection of high impedance faults by distance relays
Author :
Thakallapelli, Abilash ; Mehra, Rajesh ; Mangalvedekar, H.A.
Author_Institution :
Dept. of Electr. Eng., VJTI, Mumbai, India
fYear :
2013
fDate :
6-8 Dec. 2013
Firstpage :
374
Lastpage :
377
Abstract :
For maintaining security and reliable operation of distance relays power swing blocking is necessary to prevent maloperation during power swings and high impedance faults detection is necessary for operation of distance relays, since distance relays may treat high impedance faults as load since the fault will be out of reach of the relay. This paper proposes an algorithm for differentiation of faults from power swing and high impedance fault detection by distance relay simultaneously by a single algorithm, based on extracting current waveform components using Prony method. The merit of this method is demonstrated by simulating different high impedance faults and also during power swing conditions using the ATP version of the EMTP.
Keywords :
EMTP; electric impedance; electrical faults; fault diagnosis; power system security; relay protection; signal detection; ATP version; EMTP; Prony method; current waveform component extraction; distance relays; fault differentiation; impedance fault detection; power swing blocking; security maintenance; Circuit faults; Impedance; Power systems; Protective relaying; Signal processing algorithms; Wavelet transforms; Distance relay; decaying dc component; high impedance faults; power swings; prony method;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Condition Assessment Techniques in Electrical Systems (CATCON), 2013 IEEE 1st International Conference on
Conference_Location :
Kolkata
Print_ISBN :
978-1-4799-0081-7
Type :
conf
DOI :
10.1109/CATCON.2013.6737530
Filename :
6737530